GB/T 16293 & 16294-2025: Cleanroom Airborne and Settling Microbe Testing

GB/T 16293 & 16294-2025: Cleanroom Airborne and Settling Microbe Testing

Besides airborne particles, sterile medical device manufacturers in China have to test their cleanrooms regularly for airborne microbes or settling microbes. The two test methods are GB/T 16293, Test method for airborne microbe in clean room (zone) of the pharmaceutical industry, and GB/T 16294, Test method for settling microbe in clean room (zone) of the pharmaceutical industry. The 2025 editions take effect on 2026-11-01 and replace the 2010 editions in full, changing sampling points, sample volume, plate exposure and incubation, and dropping the "result evaluation" and "routine monitoring" clauses. Based on both editions, this article covers sampling, incubation and calculation, use in device GMP cleanroom monitoring, investigating excursions, and SUNGO Shanghai's accreditation.

Key points

  • Methods, not limits: limits come from the regulations, industry standards and company documents a manufacturer works to. The 2010 evaluation clause (5.7) is deleted in 2025.
  • New editions effective 2026-11-01: GB/T 16293-2025 and GB/T 16294-2025 were both published on 2025-10-05.
  • Airborne microbes are sampled actively: usually with a sieve impactor; minimum volume depends on grade; C = M / V × 1 000 gives CFU/m³.
  • Settling microbes are sampled passively: three more minimum points than for airborne microbes at the same area; in operation, ISO 5, Grade A, Grade B and Class 100 areas should be sampled for the whole operation. The 2010 minimum number of plates is gone.
  • Shared requirements: tryptic soy agar (TSA), with a neutralizer or Sabouraud dextrose agar (SDA) where necessary; a same-batch negative control must show no growth or the test is invalid; qualification at rest and in operation, routine monitoring in operation.
  • What SUNGO can issue: GB/T 16293 and GB/T 16294 (whole standards, no edition year) are within the IAS accreditation of SUNGO's Shanghai laboratory (TL-1019). Neither is covered by CNAS or CMA, so only IAS reports can be issued.

The standards and their scope

Editions and responsible committee

GB/T 16293 and GB/T 16294 are recommended (voluntary) national standards. Both date from 1996 and were revised in 2010 (published 2010-09-02, effective 2011-02-01) and 2025. The 2025 editions were proposed by the National Medical Products Administration (NMPA) and are under SAC/TC 106. GB/T 16292-2025 (airborne particles) shares the same dates and is covered in a separate article.

Scope, references and terms

Under clause 1 of the 2025 editions, GB/T 16293 applies to airborne microbe testing in pharmaceutical cleanrooms (zones) such as clean plants and clean laboratories, but not to online monitoring systems; GB/T 16294 covers settling microbes in the same way, without that exclusion. The only normative reference is Volume IV of the Chinese Pharmacopoeia (ChP), 2025 edition.

Airborne microbes are viable airborne microorganisms collected by active sampling (CFU/m³); settling microbes are collected by passive sampling. The at-rest and operational states follow GB/T 25915.1-2021.

Why a "pharmaceutical industry" standard applies to devices

  • GMP appendix: clause 2.7.3 of the GMP Appendix for Sterile Medical Devices (former CFDA Announcement No. 101 of 2015, in force from 2015-10-01) requires periodic testing of cleanroom particles, airborne or settling microbes, air changes or velocity, pressure differences, temperature and humidity according to the relevant device industry standards, with records kept.
  • Industry standard: Annex C of YY/T 0033-2000, Good manufacture practice for sterile medical devices (cover reads YY 0033—2000; listed as recommended and current on the national standards platform as of 2026-10-22) names GB/T 16293—1996 and GB/T 16294—1996 as the monitoring methods for airborne and settling microbes.
  • Revised device GMP: the revised device GMP takes effect on 2026-11-01. An NMPA notice of 2026-09-14 (Guo Yao Jian Xie Guan [2026] No. 14) says that from 2026-11-01, sterile and certain other devices must meet both the revised GMP and the current appendices.

The device sector has referenced these methods since the 1996 editions. Which edition and which limits apply should be taken from the company's current documents.

What changed in 2025

Based on the 2025 forewords and the text of both editions:

Topic2010 editions2025 editions
Minimum sampling pointsRefer to GB/T 16292-2010Risk-based, and at least the minimum in each standard's Table 1
Sampling point locationWorking area about 0.8 m to 1.5 m above the floor; layouts in Annex ARisk-based, horizontal and vertical; Annex A deleted
Airborne microbe sample volumeTable 1 by Class 100, 10 000, 100 000 and 300 000Table 2 adds ISO classes and Grades A to D
Settle platesRecommended minimum number of plates; 30 min or more at rest, up to 4 h in operationMinimum number of plates deleted; exposure time set under 8.2.2 and 8.2.3
Culture mediaTSA, SDA or another user-accepted, validated medium; recipes in Annex BTSA, plus neutralizer or SDA where needed; per 9203 in ChP 2025 Volume IV; Annex B deleted
IncubationTSA at 30 °C to 35 °C for at least 2 d; SDA at 20 °C to 25 °C for at least 5 dTwo-temperature schemes if the population is uncertain; SDA at 20 °C to 25 °C for 5 d to 7 d
Result evaluation, routine monitoringClauses 5.7 and 5.8Deleted

GB/T 16293: testing airborne microbes

Sampler and equipment

Clause 5.1 of the 2025 edition says a sieve impactor is generally used. The fan draws the aerosol towards a solid medium, and microbe-carrying particles travel straight on by inertia and impact on the agar. Samplers are used per their instructions and calibrated periodically; a note lists slit and centrifugal impactors, impingers and filtration samplers as other types. Incubators and steam sterilizers also need periodic calibration.

Number and location of sampling points

Clause 8.1 requires the number and position of sampling points (horizontal and vertical) to be set by risk assessment during cleanroom qualification and monitoring, using tools such as FMEA or HACCP, while meeting the minimum in Table 1. Both standards set Table 1 by room area:

Cleanroom (zone) area (m²)Airborne microbes, minimum points (GB/T 16293-2025 Table 1)Settling microbes, minimum points (GB/T 16294-2025 Table 1)
≤814
>8 to 2825
>28 to 5236
>52 to 6847
>68 to 10458
>104 to 14869
>148 to 232710
>232 to 436811
>436 to 1 000912
>1 000Formula (1)Formula (1)

Above 1 000 m², the airborne microbe minimum is NL = (27 × A / 1 000) / 3, where A is the area in m², rounded up to a whole number. The note explains that this is the GB/T 16292-2025 classification minimum divided by three, an empirical simplification.

Minimum sample volume

Under clause 8.2.2, the plate is loaded, the sample volume set and the sampler started. The minimum volume per point should follow Table 2, and each point is sampled once.

Cleanliness grade (grouped as in Table 2)Minimum sample volume (L per sample)
ISO 5, Grade A, Grade B (at rest), Class 1001 000
ISO 7, Grade B (operational), Grade C (at rest), Class 10 000500
ISO 8, Grade C (operational), Grade D (at rest), Class 100 000100
ISO 8.5, Grade D (operational), Class 300 000Not uniformly specified

Table 2 groups grades by sample volume and is not used here as an equivalence table. For Class 300 000, which had a set volume in 2010, the 2025 edition leaves the volume to the company's sampling plan.

Sampling and negative control

  • Inlet orientation: facing the airflow in unidirectional-flow cleanrooms (zones) or at supply outlets; pointing upwards in non-unidirectional cleanrooms (clause 8.2.1).
  • Negative control: a plate from the same batch is handled in the same way but not exposed. It must show no growth after incubation, otherwise the test is invalid (clause 8.2.3).

Incubation and counting

Under clause 8.3 of the 2025 edition, plates are incubated inverted. When the environmental population is uncertain, plates may be incubated at 20 °C to 25 °C for 3 d to 5 d and then at 30 °C to 35 °C for 2 d to 3 d, or the other way round: 30 °C to 35 °C for 2 d to 3 d, then 20 °C to 25 °C for 3 d to 5 d. SDA is incubated at 20 °C to 25 °C for 5 d to 7 d. The scheme should be adjusted using historical data. Colonies are counted by eye or on a colony counter.

Calculation and evaluation

Clause 8.4 gives the concentration at each point as C = M / V × 1 000, where C is in CFU/m³, M is the colony count (CFU) and V is the sample volume (L). The worked example in the 2010 edition: 400 L sampled with 1 colony gives 2.5 per m³.

Under the 2010 edition, the mean at each point had to be below the selected limit, and an at-rest exceedance needed two passing repeat samples. The 2025 edition deletes "result evaluation": the report gives each point's concentration, and pass/fail and retest rules sit in company documents.

GB/T 16294: testing settling microbes

Number and location of sampling points

Settle plates are also placed by risk assessment and must meet the minimum in the table above. Above 1 000 m², the minimum is NL = 3 + (27 × A / 1 000) / 3, rounded up. The note explains that the three extra points widen spatial coverage and make the data more representative.

Under clause 8.2.1, plates are placed at the set points and opened so that the medium is exposed to air, keeping away from return-air grilles where possible. The 2010 edition (like GB/T 16293-2010) listed working-area points about 0.8 m to 1.5 m above the floor (slightly above the work surface); the 2025 edition gives no fixed height, and vertical position is also set by risk assessment (clause 8.1).

Number of plates

Clause 5.4.2 of the 2010 edition also recommended ("should") a minimum number of φ90 mm plates in addition to the minimum points: 14 for Class 100 and 2 each for Class 10 000, 100 000 and 300 000. The 2025 edition deletes this and uses the area-based table of minimum points instead. Procedures that assign plates by class should be revised with the change of edition.

Exposure time

  • Operational testing: ISO 5, Grade A, Grade B and Class 100 areas should be sampled for the whole operation; sampling time for other grades is set by risk assessment (clause 8.2.2).
  • At-rest testing: sampling time should match that used in operational testing (same clause).
  • Exposure per plate: sampling uses an established exposure time for a single plate; where necessary, several plates are exposed in succession to cover the required sampling time (clause 8.2.3).
  • Why the single-plate time matters: per the note to 8.2.3, plates under high airflow, turbulence, heat or low humidity may dry out or change (e.g. pH), killing captured microbes; exposure under specific conditions may need study to show growth promotion is not impaired. Exposure is generally no more than 4 h.

The 2010 edition specified 30 min or more at rest and no more than 4 h in operation. Its informative Annex C states an exposure time with every settling microbe requirement it lists, so limits and exposure time go together. If sampling times change under the 2025 edition, company documents should first state whether results stay comparable with historical data and existing limits.

Incubation, counting and results

Incubation and negative control requirements are the same as for airborne microbes (clauses 8.2.4 and 8.3 of the 2025 edition). Overlapping colonies that can be told apart are counted individually.

The 2010 edition calculated the mean count per point as M̄ = (M1 + M2 + … + Mn) / n, where n is the number of plates, expressed per plate, and used the same evaluation rules as for airborne microbes. The 2025 edition deletes both "result calculation" and "result evaluation". Clause 9 requires the report to give the settling microbe count at each point, together with the medium, incubation conditions and the sampling point layout.

Using the tests in device GMP cleanroom monitoring

When to test at rest and in operation

Clause 7 of both 2025 editions requires testing in both the at-rest and operational states for cleanroom qualification, and in the operational state for routine monitoring. For at-rest tests, unidirectional-flow rooms should be tested after the HVAC system has run normally for at least 10 min, and non-unidirectional rooms after at least 30 min. The 2010 editions allowed no more than two test personnel in the room at rest.

The note to Annex C of YY/T 0033-2000 says that particles, airborne or settling microbes and the other listed parameters must meet requirements when tested at rest, and that these parameters should be tested in operation at the monitoring frequency. Clause 2.3.2 of the GMP appendix requires the air handling system to be qualified, run continuously and be requalified periodically, with the necessary testing or verification after a restart.

Airborne or settling microbes?

Clause 2.7.3 of the GMP appendix says "airborne or settling microbes". The two cannot be converted into each other because the units differ: airborne results are CFU/m³ of sampled air, settle plate results are colonies per plate and depend on the plate and exposure time. The choice and the limits follow the industry standards and company documents. Both tests are within SUNGO Shanghai's IAS accreditation.

Investigating results above limits

With "routine monitoring" deleted in 2025, investigations belong to the company's quality system. A possible order, based on both editions:

  1. Confirm the test was valid: no growth on the negative control; sample volume or exposure time, incubation temperature and time as planned.
  2. Look at extent and trend: one point or several, one-off or repeated excursions above alert or action levels (terms from the 2010 editions), compared with particle and pressure records from the same period.
  3. Look for causes: the triggers for reviewing sampling frequency in clause 5.8 of the 2010 editions make a checklist, e.g. longer-than-planned shutdowns, major HVAC maintenance during production, changed disinfection procedures, major equipment maintenance or additions, and major layout changes.
  4. Adjust the culture scheme: add SDA where fungi are suspected or for seasonal effects; use a neutralizer where necessary.
  5. Assess impact and retest: assess the impact on product and handle it through the company's deviation and CAPA procedures; retest rules are set by company procedures. For particles, clause 7.6 of GB/T 16292-2025 requires classification testing to be repeated when remediation significantly affects facilities or equipment.

Accreditation scope

The table reproduces the rows of the IAS scope of SUNGO's Shanghai laboratory (TL-1019) relevant to this article.

ItemClauseNotes / limitations
GB/T 16293 Test method for airborne microbe in clean room (zone) of the pharmaceutical industryWhole standardIAS, no edition year; no limitation listed
GB/T 16294 Test method for settling microbe in clean room (zone) of the pharmaceutical industryWhole standardIAS, no edition year; no limitation listed
GB/T 16292 Test method for airborne particles in clean room (zone) of the pharmaceutical industryWhole standardIAS, no edition year; no limitation listed (airborne particles covered in a separate article)
YY 0033 Good manufacture practice for sterile medical devicesAnnex CIAS; Accredited only for Annex C

These standards are not on the CNAS or CMA certificates of SUNGO Shanghai, and the Hefei laboratory's certificates do not include cleanroom testing.

Where SUNGO does this work and under which accreditation

  • Legal entity: Shanghai SUNGO Medical Technology Co., Ltd., laboratory at Kangqiao East Road 958, Pudong, Shanghai. Hefei SUNGO Medical Technology Co., Ltd. is a separate legal entity; its certificates do not cover these tests.
  • Accreditation: IAS only (TL-1019). Only IAS reports can be issued, not CNAS or CMA reports.
  • Edition: the IAS scope carries no edition year. Confirm with the laboratory before ordering whether the IAS report will be issued to the 2025 or the 2010 edition.
  • Location: sampling takes place in the client's cleanroom (zone). Timing, occupancy state, sampling points and media preparation are agreed at the quotation stage.
  • Report use: check with the regulator or auditor in advance whether they accept the report.

Preparing for testing

  • Floor plan: area of each room, specified cleanliness grade, supply and return-air positions, and unidirectional-flow zones.
  • Tests and acceptance basis: which tests, which document the limits come from, and the plate size and exposure time behind settle plate limits.
  • Edition: state whether the 2025 or 2010 edition applies and confirm with the laboratory.
  • Occupancy state: at rest, operational or both; for operational tests, activities, people, running equipment and the period to cover.
  • Sampling point rationale: a list of critical locations if a risk assessment has been done.
  • Media: whether a neutralizer or SDA is needed; any historical environmental microbiology data.
  • Site conditions: HVAC running times, disinfection schedule, gowning and entry procedures.

FAQ

Do we have to test both airborne and settling microbes?

GMP appendix clause 2.7.3 says "airborne or settling microbes". The choice and limits depend on your industry standards and company documents.

Can we still test to the 2010 editions after November 2026?

The 2025 editions replace the 2010 editions from 2026-11-01. If documents or a contract still specify 2010, confirm with the laboratory before ordering whether an IAS report can be issued to it.

What if the negative control shows growth?

Under clauses 8.2.3 (airborne) and 8.2.4 (settling) of the 2025 editions, growth on the negative control makes that test invalid; investigation and re-sampling follow company procedures.

How long can a settle plate be exposed?

The 2025 edition uses an established single-plate time, with successive plates to cover the sampling time; exposure is generally no more than 4 h. The 2010 edition set 30 min or more at rest and up to 4 h in operation.

Requesting a quotation

When requesting a quotation, please send the floor plan with room areas, grades and acceptance basis, the tests needed, the occupancy state, the edition and the site address. SUNGO's device testing services are listed on the Other Medical Device Testing page. For microbiological control of the product itself, see How to Determine Bioburden: Key Points of ISO 11737-1. Please send your enquiry through the Contact page.

About SUNGO Lab: What We Test

SUNGO Lab is made up of two independent companies, Shanghai SUNGO Medical Technology Co., Ltd. and Hefei SUNGO Medical Technology Co., Ltd., and focuses on medical device testing. Our core service lines are:

  • Wheelchair and mobility aid testing (Hefei laboratory): manual and powered wheelchairs, scooters, walking aids and crutches to the ISO 7176 series (excluding Part 19 crash testing and Part 20 standing wheelchairs), ANSI/RESNA WC-1/WC-2, EN 12183, EN 12184, the GB/T 18029 series and GB/T 12996-2024. Which accreditation (CNAS, CMA or IAS) covers each standard is as listed in our certificate scopes. See Wheelchair testing for FDA 510(k) and RESNA.
  • Medical electrical safety and EMC (Hefei laboratory, IAS accredited, certificate TL-1119): IEC 60601-1, IEC 60601-1-2, IEC 60601-1-8, IEC 60601-1-11 and ISO 80601-2-69, with the corresponding Chinese standards GB 9706.1 and YY 9706.102.
  • Testing for registration in China and overseas: we plan testing to the standards your target market requires (NMPA, FDA 510(k), EU CE marking and others) and issue the test reports for your submission; whether a report is accepted is decided by the regulator.

Our Shanghai laboratory also tests medical masks, gloves, surgical gowns, sterile packaging and sterilization-related items. CNAS and IAS are both signatories to the ILAC MRA. Send your product, target markets and standards through our contact page and we will confirm which laboratory and which accredited scope covers each test.

Need testing? Tell us your product and standards

Contact us directly
Phone
+86 132 4819 8029 (Mr. Gan)+86 177 5560 4650 (Mr. Luo)
E-mail
haixiao.gan@sungoglobal.comjun.luo@sungoglobal.com
Mon–Fri 9:00-18:00
WeChat QR CodeWeChatScan to add us on WeChat
Send us a message
About your personal information
  • Who collects it: Shanghai SUNGO Medical Technology Co., Ltd., the operator of this website. If the work you ask about is carried out by Hefei SUNGO Medical Technology Co., Ltd., we pass your enquiry to that company’s contact person for the same purpose.
  • What we collect: only what you type into the form above. The website’s access logs routinely record IP address and browser type, used only for security, troubleshooting and traffic statistics. Please do not enter ID numbers, medical records or other sensitive information.
  • Why: to reply to this testing enquiry. It is not used for bulk marketing; except for passing it to Hefei SUNGO Medical Technology Co., Ltd. as described above, it is not given to anyone else.
  • How long: 12 months from the day you submit it, then it is deleted. It is stored on a server in mainland China.
  • Your rights: contact us by the phone numbers or e-mail addresses above at any time to see, correct or delete what you submitted.